3200-Plus 3200 Fuel Smart HydroStat Plus Instruction Manual

June 13, 2024
HYDROSTAT

3200-Plus 3200 Fuel Smart HydroStat Plus

Product Information

The MODEL 3200-Plus Temp Limit / LWCO Control with Thermal
TargetingTM is designed for water boilers. It has a three-function
design, including temperature limit control, low water cut-off, and
boiler reset control. The control adjusts the boiler temperature
based on heating demand. It operates on 120 VAC input and has a 24
VAC burner circuit. The product is patented under patent numbers
8,931,708; 8,844,834; 7,891,572, with others pending. It also
supports the use of the Hydrolevel OS-100 Outdoor Sensor Kit (sold
separately) for outdoor reset and warm weather shut-down
functionality.

Installation of this control should be done by qualified
personnel in accordance with local codes and ordinances. It is
important to read the instructions completely before proceeding.
Safety precautions are advised, including disconnecting the power
supply before installing or servicing the control to prevent
electrical shock or equipment damage. Additionally, the boiler
should be thoroughly cooled before installing or servicing the
control to prevent serious burns.

In climates subject to sustained below-freezing temperatures,
freeze protection monitoring or other precautions are recommended
for unattended dwellings to prevent frozen pipes and water
damage.

Product Usage Instructions

  1. 1. IMMERSION WELLS

The Fuel Smart HydroStat control can be installed on a
Hydrolevel Electro-WellTM or an existing immersion well in the
boiler. When installed on an Electro-WellTM, the Low Water Cut-Off
function is automatically activated. Heat transfer grease should
not be used. Ensure there is 1/2 inch clearance between the copper
well tube and any surface within the boiler.

  1. 1. MOUNTING THE CONTROL

Make sure the immersion well or Electro-WellTM is installed in
the boiler manufacturer’s designated temperature limit control
tapping. If using an Electro-WellTM, pipe sealing compound should
be used instead of Teflon tape.

  1. 1. Two mounting positions are available on the back of the  

    control. Select the best position for the location of the control
    and remove the knockout.

  2. Place the control on the well and tighten the well clamp screw
    while holding the box against the well nut.

  3. Insert the sensor all the way into the well through the chosen
    knockout.

Note: The Fuel Smart HydroStat control can be mounted
horizontally in case of space restrictions, but vertical mounting
is recommended for proper orientation of the LED display.

MODEL 3200-Plus Temp Limit / LWCO Control with Thermal TargetingTM for Water Boilers
120 VAC Input / 24 VAC Burner Circuit PATENT NO. 8,931,708; 8,844,834; 7,891,572; others pending
Three Function Design

INSTALLATION INSTRUCTIONS and OPERATING MANUAL
· Saves Fuel ­ Features Thermal TargetingTM technology and Thermal Pre-Purge capability
· Outdoor Reset Ready ­ Provides Outdoor Reset and Warm Weather Shut-Down capability with the addition of Hydrolevel OS-100 Outdoor Sensor Kit (sold separately)
· Universal Design ­ Replaces common cold-start and triple-action Aquastats
· Operating Indicators ­ LEDs, Dynamic Display and Test Button provide continual and on-demand status checks
· Prioritizes Domestic Hot Water ­ Gives priority to low limit setting or to calls from indirect water heater
· Reduces Condensation ­ Holds circulator off until boiler reaches 125°F
·
Aquastat is a registered trademark of Honeywell International, Inc.

Temperature Limit Control Designed for cold start and tankless coil boilers.

Low Water Cut-Off Provides protection against potentially dangerous low water conditions when installed with the Hydrolevel Electro-WellTM (see page 2 for details).

Boiler Reset Control
· Thermal Targeting ­ On-board micro-
processor adjusts boiler temperature based on heating demand.
· Outdoor Reset Ready ­ Compatible with
Hydrolevel OS-100 Outdoor Sensor Kit (sold separately) for outdoor reset and warm weather shut-down functionality.

WARNING Electrical shock hazard. To prevent electrical shock, death or equipment damage, disconnect power supply before installing orservicing control. Only qualified personnel may install or service this control in accordance with local codes and ordinances. Read instructions completely before proceeding.

CAUTION To prevent serious burns, boiler should be thoroughly cooled before installing or servicing control.

WARNING Frozen pipes/water damage. Central heating systems are prone to shut down as a result of power or fuel outages, safety related fault conditions or equipment failure. Installation of freeze protection monitoring or other precautions is recommended for unattended dwellings in climates subject to sustained below-freezing temperatures.

126 Bailey Road, North Haven, CT 06473 · Phone 203-776-0473 · FAX 203-764-1711 · www.hydrolevel.com
1

IMMERSION WELLS
Fuel Smart HydroStat can be installed on a Hydrolevel Electro-WellTM or on an existing immersion well already in the boiler. IMPORTANT: The control will only provide low water cut-off protection when installed on an Electro-WellTM.
Installing HydroStat with Hydrolevel Electro-WellTM
The Electro-Well can be identified by the black electrical insulator or, if installed, by the groove cut into the hexnut.
When installed on an Electro-WellTM (sold separately), the Low Water Cut-Off function is automatically activated. Heat transfer grease should not be used. NOTE: For proper operation, there must be 1/2″ clearance between the copper well tube and any surface within the boiler.
See Electro-WellTM models on page 15.
Installing HydroStat with Standard Immersion Well
NOTE: When installed on a standard immersion well, the “LWCO Active” LED will not illuminate.
2

MOUNTING THE CONTROL

IMPORTANT Make sure that the immersion well or Electro-WellTM is installed in the boiler manufacturer’s designated temperature limit control tapping.
NOTE: If installing an Electro-Well, pipe sealing compound should be used. Teflon tape is not recommended.

STEP 1 Two mounting positions
are available on the back of the control (Fig. 1). Select which of the two positions (2 knockouts) is best for the location of the control. Remove the knockout.

STEP 2 Place control on the well.
While holding box against well nut, tighten well clamp screw. (Fig. 2)

STEP 3 Insert sensor ALL THE
WAY into well through the knockout (A or B) you have chosen. (Fig. 3)

BACK OF FUEL SMART HYDROSTAT BOX

FIG. 1

FIG. 2

FIG. 3

IMPORTANT ­ Sensor must be inserted all the way into the well for proper operation.

CORRECT

INCORRECT

NOTE: In the case of space restrictions, the Fuel Smart HydroStat control may be mounted in a horizontal orientation without any loss of function. Hydrolevel recommends vertical mounting, when possible, for proper orientation of LED display.

REMOTE MOUNTING KITS
Remote Mounting Kits are available separately for mounting the Fuel Smart HydroStat control box in a remote location. Each kit includes mounting hardware and a remote sensor.

Part No.
48-101 48-102 48-103 48-104 48-121

Description
HydroStat Remote Mount Kit with 24″ sensor HydroStat Remote Mount Kit with 48″ sensor HydroStat Remote Mount Kit with 10′ sensor HydroStat Remote Mount Kit with 20′ sensor HydroStat Pipe Mounting Kit with 48″ sensor

GROUNDING: When using Remote Mounting Kits, ensure your incoming voltage ground wire is connected to the HydroStat’s ground screw (see “GROUNDING” section on next page)

3

WIRING
WARNING Electrical shock hazard. To prevent electrical shock, death or equipment damage, disconnect power supply before installing or servicing this control.

STEP 1
Connect 120 VAC Hot to terminal L1. Connect 120 VAC Common to terminal L2. Disconnect means and overload protection as required (provided by others).

STEP 2
Connect the burner circuit to B1-B2. (B2 is common.)

STEP 3
Connect the circulator to C1-C2. (C2 is common.)

STEP 4
Connect the thermostat to T/TV.

STEP 5
If the boiler is equipped with a plug-in style vent damper, unplug the factory installed jumper from the receptacle on the circuit board and replace it with the vent damper plug.
WARNING: Failure to remove jumper can result in personal injury or death.

GROUNDING
In order to ensure proper operation, It is important to confirm that the ground wire attached to the HydroStat’s ground screw, which generally comes from the boiler’s J-box, is actually tied to the house’s ground.
If the ground attached to the HydroStat’s ground screw is insufficient for proper control operation, use one of the options below to prevent noise interference.
Option1: Install a ground wire from the ground screw in the HydroStat 3200 to a non-painted area on the appliance (ex. the screws that hold the burner cover panel in place).
Option 2: Remove the white wire from the B2 terminal on the HydroStat 3200 and reinstall it on a screw that holds the burner cover panel.
Option 3: Install a wire from the Hydrostat ground plate screw to the ElectroWell (immersion well) and secure it with a clamp.

4

WIRING continued
WARNING Electrical shock hazard. To prevent electrical shock, death or equipment damage, disconnect power supply before installing or servicing this control.
STEP 6 For Systems with Indirect Water Heaters
When installing with an indirect water heater, the signal from the indirect must be separated from the heating zone signals and wired to I1 and I2 as shown above. Calls to I1 and I2 will bypass the Thermal Targeting or Outdoor Reset feature and allow the boiler to fire to the high limit setting to heat the indirect tank. NOTE: If you choose not to separate the indirect signal from the heating zones, the Economy Feature should be turned OFF to insure that the boiler supplies adequate temperature to heat the indirect tank (see page 6).
ZONE VALVE WIRING
IMPORTANT: Use a separate transformer to power zone valves. Connecting zone valves to Z-TV may overload the HydroStat and cause a lock-out condition (see Troubleshooting on page 12 for more information). The total load, including the burner circuit, vent damper, and Z-TV connections must not exceed 1.2 amps (30 VA). Connect zone valve end-switch to T/TV as shown below.
5

SETTING THE CONTROL
Dynamic Display
Water Temperature and Real Time
Verification of Setting Adjustments.
High Temperature
Limit Setting
(100°-220°F)
Factory 180°F
“Circ Delay” LED (see page 11)
Low Temperature
Limit Setting
(OFF or 110°-220°F)
Factory OFF
Damper Power LED
Vent Damper Receptacle

Diagnostic LEDs Test/Settings Button
Jumper
Economy Dial
(OFF or LO, 1, 2, 3, 4, 5, HI) Factory 1
Indicator Light (announces heat call)
Spade Connectors for OS-100 Outdoor Sensor Kit
Differentials are automatic and will vary based on control settings and boiler temperature.

NOTE: Settings can be checked using the TEST/SETTINGS Button. See page 11 for details.
Setting the High Limit
The high limit is factory set at 190°F. To adjust, turn the HI
TEMP Dial until the desired setting is displayed. (Setting
range: 100°-220°F)
Setting the Low Limit
The low limit will maintain temperature in the boiler and should only be used for boilers with tankless coils. The low limit is factory set to OFF. Prior to adjusting, remove the
jumper (not equipped on all units) . Then turn the LOW TEMP Dial clockwise until the desired temperature is
displayed.
For proper operation, the low temperature limit setting should be at least 10° below the high limit setting.
IMPORTANT: · If the display reads OFF when the Low Limit dial is adjusted,
the dial functionality has been turned off in the Program Options. See page 9 for instructions on reactivating the dial.
· If Low Limit temperature cannot be set above 140°F, remove
jumper .
Setting the Economy Feature
The Economy Feature is factory set for a 1 zone heating sys-
tem. To adjust, turn the ECONOMY Dial until the number

displayed equals the number of heating zones. Do not include indirect water heaters in the number of heating zones. The Economy Feature conserves fuel by reducing boiler temperature (see “How Thermal Targeting Works” on page 7). If the heating system is unable to supply needed heat to the house, the ECONOMY Dial should be turned to a lower setting (example: In a three zone house, turn the dial to 2 or 1). Conversely, if the boiler provides adequate heat, added fuel savings can be achieved by selecting a higher setting (example: 4 or 5). If the heating and indirect water heater signals were not separated when wiring the control, the Economy Feature should be turned OFF to ensure the boiler supplies adequate temperature to heat the indirect tank.
SETTING
Disables economy function. Will allow boiler to fire until hilimit temp is reached and re-fire with a 10° subtractive differential.
Provides lowest level of fuel savings. Use this setting only if the house does not stay warm at higher settings.
Recommended setting for single zone systems
Recommended setting for Two zone systems
Recommended setting for Three zone systems
Recommended setting for Four zone systems
Recommended setting for Five zone systems
Provides highest level of fuel savings

6

SYSTEM START-UP
At initial start up, with the Economy Feature active, the control establishes a 145°F target temperature. To test the high limit shut-off function, the Economy Dial must be turned to OFF. Once tested, restore the Economy setting. If the heating demand is high, the target will increase over time to satisfy the heat load. NOTE: · Smart DHW Priority: During a call from an indirect water heater, the control will de-energize the circulator contacts (C1/C2) to
heat only the indirect tank ensuring an adequate supply of domestic hot water. The control will re-energize the circulator when the indirect tank is satisfied or if the boiler temperature reaches 170°F. If the indirect call continues for 45 minutes, the control will override the priority function energizing the circulator to provide space heating.
HOW THERMAL TARGETING WORKS
Thermal Targeting technology analyzes thermostat activity and continually evaluates how much heat the house requires. When it is very cold outside, the heat demand is high and the Fuel Smart HydroStat will raise the boiler’s Target temperature to provide needed heat to the home. When the outside temperature is milder, the heat demand is lower. During these periods, the Fuel Smart HydroStat will lower the boiler’s Target temperature ­ saving fuel ­ while continuing to provide comfort to the house.

RECORD YOUR SETTINGS

DATE INSTALLED

____ LOW LIMIT SETTING ____

HIGH LIMIT SETTING ____ ECONOMY SETTING ____

OPTIONAL FEATURES
NOTE: The Program Mode ­ Pro ­ is accessed by turning the
LOTEMP dial to a position just above OFF.
Thermal Pre-Purge
Thermal Pre-Purge is designed to maximize boiler efficiency. When activated, the control will supply latent heat that may remain in the boiler from a previous run cycle to the next heating zone that calls. The control monitors how quickly the boiler temperature is declining and activates the burner only when it determines that the latent heat is insufficient to satisfy the call.
Pur During the purge cycle, the display will indicate . This feature works with single-zone and multi-zone heating systems uti-
lizing circulators or zone valves. No change in wiring is needed.
To activate Thermal Pre-Purge
1. Turn the LO TEMP dial to access the Program Mode ­ indicated in the display as Pro 2. Turn the HITEMP dial to select feature 1 3. Push the Test/Settings Button to turn Thermal Pre-Purge on or OFF
4. Reset LO TEMP and HITEMP settings to desired temperatures (see page 6)
MORE OPTIONAL FEATURES ON NEXT PAGE
7

OPTIONAL FEATURES continued
Degrees Fahrenheit or Celsius c The control has the ability to operate in degrees Fahrenheit or Celsius. When operating in Celsius, a will appear in the dis-
play next to the temperature whenever the temperature is below 100 degrees.
To change between degrees Fahrenheit and degrees Celsius
1. Turn the LO TEMP dial to access the Program Mode ­ indicated in the display as Pro 2. Turn the HITEMP dial to select feature 2 3. Push the Test/Settings Button to c for Celsius or F for Fahrenheit
4. Reset LO TEMP and HITEMP settings to desired temperatures (see page 6)
Manual Reset Low Water Cut-Off
The low water cut-off operation on the HydroStat can be set to operate in automatic (default) or manual reset mode. When in manual reset mode, the control will shut-down the burner immediately when a low water condition is detected. If the low water condition is sustained for 30 seconds, the low water light will blink, indicating that the control has locked out the burner. The control can only be reset by pushing the Test Settings button on the top of the control. The manual reset feature meets CSD-1 code requirements.
IMPORTANT: The system must be checked by a qualified heating professional prior to resuming operation. WARNING: DO NOT ADD WATER UNTIL THE BOILER HAS FULLY COOLED.
To activate Manual Reset LWCO mode
1. Turn the LO TEMP dial to access the Program Mode ­ indicated in the display as Pro 2. Turn the HITEMP dial to select feature 3 3. Push the Test/Settings Button to A for Automatic Reset Mode or b for Manual Reset Mode
4. Reset LO TEMP and HITEMP settings to desired temperatures (see page 6) To Test the Manual Reset Feature: Press and hold the Test/Settings button located on the top of the control for 30 seconds to simulate a low water condition. After 30 seconds, the Low Water light will blink indicating that the control is locked out. To reset the lock-out condition, press the Test/Settings button momentarily.
Circulator Activation Options
When in the default mode, the HydroStat activates the circulator (C1/C2 contacts) on calls to T/TV. The control can be programmed to activate the circulator on calls to I1/I2 in place of, or in addition to, calls to T/TV.
To change how the Circulator is activated
1. Turn the LO TEMP dial to access the Program Mode ­ indicated in the display as Pro 2. Turn the HITEMP dial to select feature 4
3. Push the Test/Settings Button to select between the following options:
A – Circulator on T/TV call only b – Circulator on I1/I2 call only C – Circulator on both T/TV & I1/I2 calls
4. Reset LO TEMP and HITEMP settings to desired temperatures (see page 6)
MORE OPTIONAL FEATURES ON NEXT PAGE
8

OPTIONAL FEATURES continued
Circulator Hold Off (Enhanced Condensing Protection)
To reduce the potential for condensing, on a call for heat the control will allow the boiler to heat to 125°F prior to energizing the circulator. Once energized, the circulator will remain on for the duration of the heating call unless the boiler temperature drops below 115°F. If this occurs, the circulator will re-energize when the boiler returns to 125°F. The blue LED above the vent damper plug will light to indicate the control is in “circulator hold off” mode. Circulator Hold Off will expire after 15 minutes.
To activate Circulator Hold Off
1. Turn the LO TEMP dial to access the Program Mode ­ indicated in the display as Pro 2. Turn the HITEMP dial to select feature 5 3. Push the Test/Settings Button to turn Circulator Hold Off on or OFF
4. Reset LO TEMP and HITEMP settings to desired temperatures (see page 6)
Low Limit Setting
The low limit temperature setting is designed for boilers equipped with tankless coils. When set, the control will operate the
burner to maintain the set point temperature in the boiler at all times. This setting should be turned to OFF (fully counterclock-
wise) when the boiler does not have a tankless coil. This optional program feature provides for disabling the low limit dial so that it cannot be turned on inadvertently. Use the instructions below to deactivate or reactivate the low limit dial functionality.
To disable the Low Limit Setting
1. Turn the LO TEMP dial to access the Program Mode ­ indicated in the display as Pro 2. Turn the HITEMP dial to select feature 7 3. Push the Test/Settings Button to turn Low Limit Function to on or OFF
4. Reset LO TEMP and HITEMP settings to desired temperatures (see page 6)
Setting the Well Type (Electro-Well vs. Standard Immersion Well)
When used to replace older temperature-only controls, the HydroStat can be installed on the existing well. (The Hydrolevel Electro-Well is required to activate low water cut-off operation ­ see page 2 for details). Older wells may contain hardened heat transfer grease or other contaminants that could interfere with metal-to-metal continuity between the sensor head and the inside of the well. Insufficient contact could lead to false low water conditions and burner shut downs. Setting the well type to Standard Well prevents the possibility of this occurring.
To change the well type
1. Turn the LO TEMP dial to access the Program Mode ­ indicated in the display as Pro 2. Turn the HI TEMP dial to select feature 8 3. Push the Test/Settings Button to select A for Electro-Well or b for Standard Well.
NOTE: To ensure that the low water cut-off is always active when the control is installed on an Electro-Well, setting b will ONLY be available
when installed on a standard well. The Hydrostat sensor checks to determine if a standard well is used by looking for low resistance to ground,
a condition that can only exist with a standard well. If you are installing on a standard well and either Low Water LED’s are on, setting b will not
be available. Check to see if the inside of the well tube is badly oxidized or contaminated with heat transfer grease. It may be necessary to
clean the well to allow for setting b to be selected (See Troubleshooting Guide on page 12 for more information).
RESTORING FACTORY DEFAULT SETTINGS ON NEXT PAGE
9

OPTIONAL FEATURES continued
High Limit Differential
When the Economy feature is on, the control’s Thermal Targeting feature actively sets varying differentials based on system conditions. This option allows for selecting a 10, 20 or 30 degree fixed differential when the Economy feature is turned OFF. These optional differential settings are subtractive from the HIGH LIMIT setting. Note: If the Economy feature is on, this setting will be overridden by the control’s Thermal Targeting function.
To change the high limit differential
1. Turn the LO TEMP dial to access the Program Mode ­indicated in the display as Pro 2. Turn the HI TEMP dial to select feature 9 3. Push the Test/Settings Button to select a high limit differential of 10, 20, or 30
4. Reset LO TEMP and HI TEMP settings to desired temperatures (see page 7)
Restore Factory Default Settings

To restore all features to the factory default settings (see following chart for default settings)
1. Turn the LO TEMP dial to access the Program Mode ­ indicated in the display as Pro 2. Turn the HITEMP dial to select feature dEf 3. Push the Test/Settings Button to Y to reset all features to the default settings.
4. Reset LO TEMP and HITEMP settings to desired temperatures (see page 6)

Dial Setting

Feature

Options

Description

Default Setting

1 Thermal Pre-Purge OFF Purge Inactive on Purge Active

OFF

2 Fahrenheit or Celsius F c

Degrees Fahrenheit Degrees Celsius

F

3

LWCO Manual or

Automatic Reset

A

Automatic Reset

b

Manual Reset

A

4

Circulator Options

A

Circulator operation on TT call only

b

Circulator operation on I1/I2 call only

c

Circulator operation on call from either

A

5 Circulator Hold Off on Circulator Hold Off ­ Active OFF Circulator Hold Off ­ Inactive

on

6

Not available on this control

7

Low Limit Dial

on Low Limit Dial ­ Functional

OFF Low Limit Dial ­ Disabled

on

8

Well Type

A

Hydrolevel Electro-Well

b

Standard Immersion Well

A

9

High Limit Differential

10

10° Differential

20 20° Differential

10

30 30° Differential

dEF Restore Factory
Defaults

Y

Restore Defaults

n

Do Not Restore Defaults

n

NOTE: If the HydroStat is factory-equipped on a boiler, some options may be set differently from the default settings. Not all features are available on older HydroStat models.

SEE PAGE 6 FOR ADDITIONAL SETTINGS

10

LED LEGEND and TEST/SETTINGS BUTTON

TEMP ACTIVE Indicates that the Fuel Smart
HydroStat control is powered and that the temperature function is active.
TEMP HI TEMP Illuminates when the boiler water
temperature reaches the high limit setting. It will remain lit until the water temperature falls 10°. The Fuel Smart HydroStat prevents burner operation while this LED is on. See Differential explanation on page 6.
LWCO ACTIVE Indicates that the low water cut-off
(LWCO) function of the Fuel Smart HydroStat is active. When the control is installed with a Hydrolevel Electro-Well, this LED will be on at all times when the control is powered. IMPORTANT: If the control is installed with a well other than the Electro-Well, this LED will not illuminate indicating that the control is not providing low water cut-off functionality.
LWCO LOW WATER Indicates that the boiler is in a
low water condition. The HydroStat control will prevent burner operation during this condition. If the LOWWATER light is blinking, the control has been programmed to provide lock-out protection in the event a low water condition is detected (see Manual Reset Low Water Cut-Off on page 8). Pressing the TEST/SETTINGS button will reset the control.
IMPORTANT: The system must be checked by a qualified heating professional prior to resuming operation.
WARNING: ALLOW THE BOILER TO FULLY COOL BEFORE ADDING WATER.
ECONOMY ACTIVE Indicates that the Thermal
Targeting function is active and the Fuel Smart HydroStat will reduce boiler temperature to conserve fuel. The Economy feature is activated using the ECONOMY dial. (See “How Thermal Targeting Works” on page 7 for more information).
ECONOMY TARGET When the Economy feature is
active, the Fuel Smart HydroStat continually sets target temperatures below the high limit setting to maximize fuel efficiency. When the boiler water reaches the target temperature, the LED illuminates and the burner will shut down. The boiler water will continue to circulate and heat the house as long as the thermostat call continues. The LED will stay lit until the boiler temperature drops below the differential set point at which point the boiler will be allowed to fire again. See Differential explanation on page 6. NOTE: This LED illuminates regularly during normal boiler operation.

TEST/SETTINGS Button
To Test Low Water Cut-Off: Press and hold the Test/ Settings button for 5 seconds. The display will read LCO.
LWCO TEST 00
The red Low Water light should illuminate and the burner circuit (B1 and B2) should de-energize. NOTE: The control must be installed with a Hydrolevel Electro-Well for low water cut-off functionality (see page 2 for more details). To View Current Settings: Press and release the Test/Settings Button in short intervals to sequentially display the following settings:
HIGH LIMIT SETTING 00
LOW LIMIT SETTING 00
ECONOMY SETTING 000
CURRENT TARGET TEMPERATURE The display will return to boiler temperature (default) if
Test/Settings Button in not pressed for 5 seconds.
DAMPER POWER LED
Indicates the control is energizing the vent damper. For applications where the vent damper is not plugged into the HydroStat, the LED indicates that the burner circuit (B1 – B2) is powered. If this LED is on and the burner is not firing: 1. Make sure the plug connection (or jumper, on boilers
where vent damper plug is not used) is secure. 2. Make sure that the plug connection at the vent damper
end is secure and oriented correctly. 3. Make sure damper motor turns 4. Verify the damper end switch has closed
Carbon Monoxide Hazard: If the burner DANGER fires when the vent damper is not fully opened or there is any other blockage in the flue, dangerous flue products, such as carbon monoxide, will escape into the living space causing severe personal injury or death. The flue as well as the vent damper must be checked for proper operation before allowing the system to operate.
Circ Delay LED
The blue “circ delay” LED lights to indicate the heating circulator (terminal C1) is being held off. See Circulator Hold Off (option 5) top of page 9 for more information.

11

TROUBLESHOOTING

Burner Will Not Fire

See Flow Chart 1, page 13

Burner Will Not Shut Down Temperature Display Exceeds
High Limit Setting
No or Insufficient Domestic Hot Water
Low Water Light (Red LED) is On
or Blinking
Boiler Will Not Maintain Low Limit Temperature
House Will Not Get or Stay Warm

See Flow Chart 2, page 14
Under normal operation, boiler temperature will continue to rise after the control shuts off the burner. This condition, known as “thermal stacking”, results from hot boiler surfaces continuing to release heat into the boiler water.
For boilers equipped with a tankless coil, make sure the low limit setting on the HydroStat is set properly. NOTE: If the low limit setting is dialed fully counter clockwise, it will shut off the low temperature maintenance feature and will function as a cold start control. If installed with an indirect water heater, verify that the end switch in the relay box controlling the indirect water heater is connected to the I1-I2 terminals. This will ensure that the domestic water calls are prioritized. (see “Heating and Indirect Water Heater” on page 6).
WARNING: A low water condition is a serious and potentially dangerous condition. Do not attempt to add water to a hot boiler. Allow the boiler to fully cool before adding water.
When Installed on an Electro-WellTM
When the LOW WATER light is on, this indicates that the control is not detecting water in the boiler. When the LOW WATER light is blinking, this indicates that the control has been programmed to provide low water lock-out protection and is currently locked out (see Manual Reset Low Water Cut-Off on page 8). Pressing the TEST/SETTINGS button after the low water condition is resolved will reset the lock-out condition.
1. If the light is on and the heating system is filled with water, pull the sensor out of the well and inspect it. Make sure that the metal clip is protruding enough to come in contact with the inside of the well tube. Check that the well does not have excessive build-up of heat transfer grease that may interfere with the clip contacting the well.
2. Remove well and examine for excessive residue build-up. Clean and re- install.
When Installed on a Standard Immersion Well
If either LWCO LED lights are illuminated and the control is installed on a standard immersion well, this is a false reading caused by a loss of continuity between the sensor and the inside of the well tube. Follow steps 1 and 2 (above) to ensure that the metal sensor head is making good contact with the inside surface of the copper well.
Check for overlapping high temperature setting. If the high limit setting is set below the low limit setting, the control will default to the high limit setting and the corresponding high limit differential setting.
1. Check for air-bound radiators. 2. Check thermostat settings including heat anticipator settings (common on non-digital
thermostats). 3. Check the Economy setting. The Economy feature, much like outdoor reset controls,
lowers average boiler temperature and can slow or, in some cases, prevent the house from coming up to temperature. Move to a lower setting (see “Setting the Economy Feature” on page 6).

Circulator Contacts C1 and C2 Not Energized
on Call for Heat

If the Circulator Hold Off is active (see page 9), check to see that boiler water is at or above 125°F. On a call for heat, the control will not permit the circulator to operate if the boiler water temperature is below 125°F.

All LED Lights and Temp Display are Blinking

If the LED lights and the temp display are blinking alternately, this indicates the control has sensed a boiler temperature of 250°F. When this occurs, the control pulses the burner relay and then shuts down and locks out the burner until the temperature falls below 210°F. The system should be analyzed to determine the cause of the overheating condition. Check that the sensor is inserted all the way into the well so it can accurately sense the temperature of the boiler water. Check system wiring and operation as well as the control’s high limit setting. If the cause of the overheating condition cannot be determined, the control should be replaced.

Snr in display

Check sensor connection or replace sensor.

Temperature Display Flickering Confirm proper grounding of control (see page 4) Control Continually Resets Confirm proper grounding of control (see page 4)

12

Troubleshooting Flow Chart 1 ­ Burner Will Not Fire

Does the Display Read YES
?

The Control is Purging Latent Heat from the
Boiler.

The Thermal Pre-Purge feature holds off the burner until the control determines if the latent heat in the boiler can satisfy the heat call.

NO

Is the
Green LED (TEMP ACTIVE) NO
On?

The Control is Not Powered.

The Temp Active LED will be on at all times when the control is powered.
Check for 120 VAC on terminals L1 and L2.

YES
Is the Red LED (LOW WATER) YES
On?
NO

The Control is Sensing
Low Water.

CAUTION ­ ALWAYS ALLOW A BOILER TO COOL BEFORE ADDING WATER The burner will not fire until the low water condition is satisfied. Check that the system is filled with water. Check that the sensor is inserted fully into the well and contact
between its spring clip and the copper well tube is made. Check that the control is tightly clamped to the well.
Also see page 12 for additional troubleshooting information.

Is the

Yellow LED

(HI TEMP)

YES

On?

NO

Is the

Yellow LED

(TARGET)

YES

On?

NO

Is the

Thermostat

(T/TV) Calling

NO

for Heat?

YES

Is There

24 VAC

Between B1

YES

and B2?

NO

Replace Control

The Control is Sensing High Temperature.

The burner will not fire until the boiler water has dropped to the high limit differential set-point (10° below high limit setting).
Check that the high temperature setting is correct.

The Boiler has Reached the
Target Temperature.

When the ECONOMY function is active, the control monitors heating demand and establishes Target boiler temperatures below the high limit setting to conserve fuel (see “How Thermal Targeting Works” on page 7). The burner will not fire until the boiler temperature drops to the automatically calculated Target Temp Differential.

Is the Indirect (I1-I2) Calling NO for Heat?
YES

Is the Low Limit Dial YES
Set to OFF?
NO

When the low temperature setting is set to OFF, the HydroStat will act as a cold start control. The burner will not fire unless there is a call from the thermostat (T/TV) or an external zone (I1/I2).
Set thermostat to call for heat. Burner should fire.
If the boiler has a tankless coil, set the Low Temperature Limit to maintain temperature.

The Control is Operating
Properly.

HydroStat is supplying 24 VAC to the burner circuit. Recheck wiring and operation of burner and other limit controls.

If both the red and yellow LEDs are off and there is a call to fire the burner, there will be 24 VAC on terminals B1 and B2.
If 24 VAC is not present, the control should be replaced.

13

Troubleshooting Flow Chart 2 ­ Burner Will Not Shut Down

Is the Red LED (LOW WATER) YES
On?

The Control is Sensing
Low Water.

NO

Is either Yellow LED
On?

YES

The Control has Reached Target or High Limit Temperature.

NO

Is the Thermostat (T/TV) Calling YES for Heat?
NO

The Control is Operating Normally.

Is the Indirect (I1/I2) Calling YES for Heat?
NO

The Control is Operating Normally.

WARNING!
TURN OFF POWER TO BURNER IMMEDIATELY! CAUTION ­ ALWAYS ALLOW A BOILER TO FULLY COOL BEFORE ADDING WATER. Recheck wiring. Make sure that burner is wired to
B1. Burner should never fire when red or yellow LED is lit.
The burner will continue to fire when there is a call from the thermostat or external zone.

Is the Low Limit Dial NO
Set to OFF?

Check temperature display. When the Low Limit is set, the HydroStat will fire the burner until the temperature reaches the Low Limit Setting.

YES

Is there 24 VAC between NO
B1 and B2?

Recheck Wiring.

When there is no call to fire the burner, the voltage should be 0 volts between B1 and B2.
Make sure the burner is wired to B1.

YES

Replace Control.

If there is no call for heat (from T/TV, I1/I2 or Low Limit), there should be 0 VAC between B1-B2.
If there is voltage between B1-B2, the control should be replaced.

14

MAINTENANCE
Remove the Electro-Well from the heating system every five years and clean any scale or sediment deposits from all parts that are exposed to the boiler water. After cleaning, reinstall the well using pipe sealing compound. Teflon tape is not recommended.

ELECTRO-WELLS
Fuel Smart HydroStat installed with Electro-WellTM
When installed with the Hydrolevel Electro-Well, Fuel Smart HydroStat will provide both temperature and low water cut-off functionality. If the control was supplied by the boiler manufacturer, it was installed with an Electro- Well. The Electro-Well is available separately for field installations.

1/2″ CLEARANCE 1/2″ CLEARANCE

1/2″ CLEARANCE

IMPORTANT: For proper operation of the low water cut-off function, there must be a minimum of ½” clearance between the copper well tube and any surface within the boiler.

Electro-WellTM Models

15

OUTDOOR SENSOR KITS
Hydrolevel’s optional Outdoor Sensor Kits automatically activate outdoor reset functionality and warm weather shutdown capability when plugged into the Fuel Smart HydroStat control. These kits are available separately at Hydrolevel distributors.
Part No. Description
48-140 Model OS-100 Outdoor Sensor Kit 48-145 Model OS-200 Wireless Outdoor Sensor Kit

Model OS-100

DIMENSIONS

Model OS-200

SPECIFICATIONS FUEL SMART HYDROSTAT MODEL 3200-Plus

Input voltage Burner contacts Circulator contacts Operating range ­ low limit Operating range ­ high limit Operating range ­ differentials Thermostat heat anticipator setting

120 VAC, 60 HZ 30 VA @ 24 VAC 5.8 FLA, 34.8 LRA@120 VAC Off or 110°F (43°C) – 200°F (93°C) 100°F (38°C) – 220°F (104°C) Automatic 0.2A

LIMITED MANUFACTURER’S WARRANTY

We warrant products manufactured by Hydrolevel Company to be free from defects in material and workmanship for a period of two years from the date of manufacture or one year from the date of installation, whichever occurs first. In the event of any claim under this warranty or otherwise with respect to our products which is made within such period, we will, at our option, repair or replace such products or refund the purchase price paid to us by you for such products. In no event shall Hydrolevel Company

be liable for any other loss or damage, whether direct, indirect, incidental or consequential. This warranty is your EXCLUSIVE remedy and shall be IN PLACE OF any other warranty or guarantee, express or implied, including, without limitation, any warranty of MERCHANTABILITY or fitness for a particular purpose. This warranty may not be assigned or transferred and any unauthorized transfer or assignment thereof shall be void and of no force or effect.

126 Bailey Road, North Haven, CT 06473 · Phone 203-776-0473 · FAX 203-764-1711 · www.hydrolevel.com

16

3200P-021622

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals